Backflow assembly test · Hilltop Grill
ApprovedFiled Aug 17, 2025 by Cameron Kessler, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Aug 17, 2025
- Assembly type
- RP
- Serial number
- K839582
- Size
- 1 1/2
- Test gauge serial
- G-4069
- Gauge calibration date
- Oct 28, 2024
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-17-01184
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
477 Ridgeview Dr
Owner: Fairley Holdings LLC
Parcel 013-17-01184