← Backflow review queue
Backflow assembly test · 168 Stone Gate Dr
ApprovedFiled Oct 31, 2025 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Oct 31, 2025
- Assembly type
- RP
- Serial number
- K816844
- Size
- 3/4
- Test gauge serial
- G-2125
- Gauge calibration date
- Jun 21, 2024
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-97-01055
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
168 Stone Gate Dr
Owner: Sam Benton
Parcel 013-97-01055