Backflow assembly test · 492 Mill Creek Way
ApprovedFiled Jul 20, 2026 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Jul 20, 2026
- Assembly type
- PVB
- Serial number
- Z406972
- Size
- 3/4
- Test gauge serial
- G-3678
- Gauge calibration date
- May 30, 2025
- Check valve 1
- 5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-77-01225
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
492 Mill Creek Way
Owner: Taylor Harlow
Parcel 013-77-01225