← Backflow review queue
Backflow assembly test · Main Street Elementary School
ApprovedFiled May 31, 2026 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- May 31, 2026
- Assembly type
- DC
- Serial number
- K511565
- Size
- 1
- Test gauge serial
- G-8277
- Gauge calibration date
- Mar 12, 2026
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-89-01214
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3468 Old Church Way
Owner: Danner Holdings LLC
Parcel 013-89-01214