← Backflow review queue
Backflow assembly test · 4057 Meadow Lark Way
ApprovedFiled Aug 21, 2024 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 21, 2024
- Assembly type
- RP
- Serial number
- B910512
- Size
- 3/4
- Test gauge serial
- G-1611
- Gauge calibration date
- Nov 2, 2023
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-55-01041
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4057 Meadow Lark Way
Owner: Riley Danner
Parcel 014-55-01041