← Backflow review queue
Backflow assembly test · 4057 Meadow Lark Way
ApprovedFiled Aug 9, 2025 by Jamie Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Aug 9, 2025
- Assembly type
- RP
- Serial number
- B910512
- Size
- 3/4
- Test gauge serial
- G-3611
- Gauge calibration date
- Nov 16, 2024
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-55-01041
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4057 Meadow Lark Way
Owner: Riley Danner
Parcel 014-55-01041