← Backflow review queue
Backflow assembly test · 2250 Quarry Ln
ApprovedFiled Sep 9, 2025 by Jamie Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Sep 9, 2025
- Assembly type
- DC
- Serial number
- W170102
- Size
- 1
- Test gauge serial
- G-5520
- Gauge calibration date
- Feb 5, 2025
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-88-01312
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2250 Quarry Ln
Owner: Jordan Kessler
Parcel 014-88-01312