Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Animal Hospital

Approved

Filed Sep 5, 2026 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Sep 5, 2026
Assembly type
RP
Serial number
A340548
Size
4
Test gauge serial
G-7098
Gauge calibration date
Jun 3, 2026
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-40-01076
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7902 Turkey Hill Dr
Owner: Pruitt Holdings LLC
Parcel 014-40-01076