Backflow assembly test · 6621 Sycamore Way
ApprovedFiled Jun 23, 2026 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 23, 2026
- Assembly type
- RP
- Serial number
- A843148
- Size
- 3/4
- Test gauge serial
- G-9330
- Gauge calibration date
- Sep 6, 2025
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-64-01250
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6621 Sycamore Way
Owner: Avery Benton
Parcel 014-64-01250