← Backflow review queue
Backflow assembly test · 6977 Fox Run Way
Needs reviewFiled Nov 23, 2026 by Reese Stroud, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Nov 23, 2026
- Assembly type
- RP
- Serial number
- Z851252
- Size
- 3/4
- Test gauge serial
- G-5411
- Gauge calibration date
- Feb 8, 2026
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-49-01260
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Property
6977 Fox Run Way
Owner: Jamie Ellery
Parcel 014-49-01260