← Backflow review queue
Backflow assembly test · 3929 Orchard Ct
ApprovedFiled May 20, 2026 by Jamie Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- May 20, 2026
- Assembly type
- RP
- Serial number
- A568377
- Size
- 1
- Test gauge serial
- G-3461
- Gauge calibration date
- Mar 20, 2026
- Check valve 1
- 6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-72-01357
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3929 Orchard Ct
Owner: Morgan Kessler
Parcel 014-72-01357