Backflow assembly test · 6086 Quarry Rd

Approved

Filed Sep 13, 2026 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Sep 13, 2026
Assembly type
DC
Serial number
B428690
Size
1
Test gauge serial
G-8031
Gauge calibration date
Feb 4, 2026
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-45-01243
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.