Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6489 Stone Gate Way

Approved

Filed Nov 30, 2025 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Nov 30, 2025
Assembly type
RP
Serial number
B310424
Size
3/4
Test gauge serial
G-4693
Gauge calibration date
Mar 6, 2025
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-61-01238
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6489 Stone Gate Way
Owner: Riley Kessler
Parcel 014-61-01238