Backflow assembly test · Maple Leaf Market
ApprovedFiled Jul 18, 2026 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 18, 2026
- Assembly type
- RP
- Serial number
- W192054
- Size
- 4
- Test gauge serial
- G-7603
- Gauge calibration date
- Dec 26, 2025
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-67-01293
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3736 Ridgeview Ln
Owner: Okafor Holdings LLC
Parcel 014-67-01293