Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Bakery

Approved

Filed May 11, 2024 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone

Report

Date of service
May 11, 2024
Assembly type
RP
Serial number
Z760659
Size
4
Test gauge serial
G-4004
Gauge calibration date
Jul 8, 2023
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-49-01285
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

900 Laurel Way
Owner: Benton Holdings LLC
Parcel 014-49-01285