Backflow assembly test · Blue Heron Self Storage
ApprovedFiled Oct 4, 2024 by Jamie Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Oct 4, 2024
- Assembly type
- RP
- Serial number
- B151018
- Size
- 1 1/2
- Test gauge serial
- G-7796
- Gauge calibration date
- Jul 26, 2023
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-61-01353
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2804 Ridgeview Ln
Owner: Ramirez Holdings LLC
Parcel 014-61-01353