Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 619 Orchard Rd

Approved

Filed May 30, 2025 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone

Report

Date of service
May 30, 2025
Assembly type
RP
Serial number
K793986
Size
3/4
Test gauge serial
G-8403
Gauge calibration date
Nov 20, 2024
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-15-01171
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

619 Orchard Rd
Owner: Quinn Brandt
Parcel 014-15-01171