← Backflow review queue
Backflow assembly test · 4811 Spring Branch Way
Needs reviewFiled Nov 17, 2026 by Rowan Nguyen, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 17, 2026
- Assembly type
- RP
- Serial number
- W733460
- Size
- 3/4
- Test gauge serial
- G-8361
- Gauge calibration date
- Jun 6, 2026
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-51-01086
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
4811 Spring Branch Way
Owner: Quinn Lindqvist
Parcel 031-51-01086