Backflow assembly test · 1205 Quarry Way
ApprovedFiled Feb 13, 2026 by Logan Wexler, Patriot Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Feb 13, 2026
- Assembly type
- RP
- Serial number
- W273265
- Size
- 1
- Test gauge serial
- G-1801
- Gauge calibration date
- Oct 2, 2025
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-15-01251
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.