Backflow assembly test · 898 Quarry Ln

Filed Nov 17, 2026 by Jamie Calloway, Ridge Backflow Testing · filed from phone

Report

Date of service
Nov 17, 2026
Assembly type
RP
Serial number
W884854
Size
3/4
Test gauge serial
G-4794
Gauge calibration date
Sep 10, 2026
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-22-01316
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.