Backflow assembly test · 725 Hickory Dr

Approved

Filed Sep 4, 2025 by Sam Okafor, Summit Backflow Testing · filed from phone

Report

Date of service
Sep 4, 2025
Assembly type
RP
Serial number
B542170
Size
3/4
Test gauge serial
G-5956
Gauge calibration date
Dec 18, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-22-01269
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

725 Hickory Dr
Owner: Emerson Harlow
Parcel 035-22-01269