← Backflow review queue
Backflow assembly test · Blue Heron Bakery
ApprovedFiled Apr 18, 2025 by Sam Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- Apr 18, 2025
- Assembly type
- RP
- Serial number
- B761091
- Size
- 1 1/2
- Test gauge serial
- G-7427
- Gauge calibration date
- Jul 27, 2024
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-48-01340
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1273 Sycamore Ln
Owner: Danner Holdings LLC
Parcel 035-48-01340