← Backflow review queue
Backflow assembly test · Blue Heron Bakery
ApprovedFiled Apr 19, 2026 by Sam Okafor, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 19, 2026
- Assembly type
- RP
- Serial number
- B761091
- Size
- 1 1/2
- Test gauge serial
- G-6438
- Gauge calibration date
- Sep 26, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-48-01340
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1273 Sycamore Ln
Owner: Danner Holdings LLC
Parcel 035-48-01340