Backflow assembly test · 4224 Turkey Hill Dr

Approved

Filed Nov 1, 2026 by Jamie Calloway, Ridge Backflow Testing · filed from phone

Report

Date of service
Nov 1, 2026
Assembly type
RP
Serial number
A445035
Size
3/4
Test gauge serial
G-3253
Gauge calibration date
May 16, 2026
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-87-01038
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.