Backflow assembly test · Riverside Market
ApprovedFiled Apr 4, 2026 by Sam Okafor, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 4, 2026
- Assembly type
- RP
- Serial number
- B200878
- Size
- 2
- Test gauge serial
- G-6915
- Gauge calibration date
- Feb 23, 2026
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-96-01307
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6243 Pine Knoll Rd
Owner: Calloway Holdings LLC
Parcel 035-96-01307