Backflow assembly test · 190 Meadow Lark Trl

Approved

Filed Jan 14, 2025 by Quinn Okafor, Ridge Backflow Testing · filed from phone

Report

Date of service
Jan 14, 2025
Assembly type
RP
Serial number
Z121285
Size
3/4
Test gauge serial
G-3196
Gauge calibration date
Nov 3, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-78-01090
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

190 Meadow Lark Trl
Owner: Blake Danner