Backflow assembly test · 190 Meadow Lark Trl
ApprovedFiled Dec 28, 2025 by Quinn Okafor, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 28, 2025
- Assembly type
- RP
- Serial number
- Z121285
- Size
- 3/4
- Test gauge serial
- G-2592
- Gauge calibration date
- Apr 21, 2025
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 035-78-01090
- Readings in range, no flags
- Result: passing. Next due date resets when approved.