Backflow assembly test · 1543 Laurel Rd

Approved

Filed May 31, 2025 by Riley Ramirez, Keystone Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
May 31, 2025
Assembly type
DC
Serial number
Z521328
Size
3/4
Test gauge serial
G-1005
Gauge calibration date
Jul 3, 2024
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-22-01093
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.