El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Dental

Approved

Filed Sep 17, 2024 by Riley Ramirez, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Sep 17, 2024
Assembly type
RP
Serial number
K419006
Size
1
Test gauge serial
G-3065
Gauge calibration date
Feb 18, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-32-01115
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5100 Quarry Rd
Owner: Danner Holdings LLC
Parcel 041-32-01115