← Backflow review queue
Backflow assembly test · 566 Sycamore Trl
ApprovedFiled Jul 22, 2026 by Alex Danner, Keystone Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 22, 2026
- Assembly type
- DC
- Serial number
- A517439
- Size
- 3/4
- Test gauge serial
- G-2786
- Gauge calibration date
- Oct 21, 2025
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-64-01236
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
566 Sycamore Trl
Owner: Shawn Hollins
Parcel 041-64-01236