El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Apartments

Approved

Filed Oct 6, 2024 by Rowan Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Oct 6, 2024
Assembly type
RP
Serial number
Z822609
Size
2
Test gauge serial
G-8375
Gauge calibration date
Jan 17, 2024
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-33-01055
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3188 Cedar Hollow Ln
Owner: Brandt Holdings LLC
Parcel 041-33-01055