Backflow assembly test · 6300 Fox Run Dr
ApprovedFiled Oct 20, 2025 by Morgan Harlow, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 20, 2025
- Assembly type
- DC
- Serial number
- B425147
- Size
- 1
- Test gauge serial
- G-6665
- Gauge calibration date
- Apr 4, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-39-01085
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.