El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Self Storage

Approved

Filed Jul 24, 2026 by Reese Vance, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jul 24, 2026
Assembly type
RP
Serial number
W963252
Size
1
Test gauge serial
G-7456
Gauge calibration date
Mar 11, 2026
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-46-01178
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7996 Ridgeview Trl
Owner: Benton Holdings LLC
Parcel 041-46-01178