← Backflow review queue
Backflow assembly test · 9343 Meadow Lark Way
ApprovedFiled Apr 30, 2025 by Morgan Harlow, Summit Backflow Testing · filed from phone
Report
- Date of service
- Apr 30, 2025
- Assembly type
- PVB
- Serial number
- W407032
- Size
- 3/4
- Test gauge serial
- G-7132
- Gauge calibration date
- Mar 11, 2025
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-68-01228
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9343 Meadow Lark Way
Owner: Shawn Vance
Parcel 041-68-01228