Backflow assembly test · 7621 Quarry Way

Approved

Filed Dec 21, 2024 by Alex Danner, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Dec 21, 2024
Assembly type
RP
Serial number
Z499375
Size
3/4
Test gauge serial
G-3698
Gauge calibration date
Aug 17, 2024
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-29-01180
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.