El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Apartments

Approved

Filed Oct 12, 2025 by Rowan Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Oct 12, 2025
Assembly type
RP
Serial number
B909925
Size
4
Test gauge serial
G-8988
Gauge calibration date
Jul 18, 2025
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-45-01070
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9239 Spring Branch Dr
Owner: Vance Holdings LLC
Parcel 041-45-01070