El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Dental

Approved

Filed May 7, 2025 by Reese Vance, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
May 7, 2025
Assembly type
RP
Serial number
B886072
Size
1 1/2
Test gauge serial
G-4772
Gauge calibration date
Oct 27, 2024
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-24-01050
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3153 Turkey Hill Ln
Owner: Harlow Holdings LLC
Parcel 041-24-01050