Gilpin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8322 Ridgeview Trl

Approved

Filed Jun 30, 2025 by Blake Fairley, Valley Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Jun 30, 2025
Assembly type
RP
Serial number
K825568
Size
1
Test gauge serial
G-9407
Gauge calibration date
May 26, 2025
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 047-71-01250
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8322 Ridgeview Trl
Owner: Logan Marsh
Parcel 047-71-01250