← Backflow review queue
Backflow assembly test · Crossroads Medical Offices
ApprovedFiled Jun 11, 2025 by Blake Fairley, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jun 11, 2025
- Assembly type
- DC
- Serial number
- K838218
- Size
- 1
- Test gauge serial
- G-3266
- Gauge calibration date
- Dec 6, 2024
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 047-19-01311
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7582 Hickory Ct
Owner: Kessler Holdings LLC
Parcel 047-19-01311