Backflow assembly test · 6318 Meadow Lark Ct

Approved

Filed Dec 25, 2024 by Blake Fairley, Valley Backflow Testing · filed from phone

Report

Date of service
Dec 25, 2024
Assembly type
RP
Serial number
A821374
Size
3/4
Test gauge serial
G-5687
Gauge calibration date
Jun 19, 2024
Check valve 1
0.9 psid
Check valve 1 closed tight
No
Check valve 2
3.7 psid
Relief valve opened at
2.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 047-21-01270
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6318 Meadow Lark Ct
Owner: Jordan Marsh
Parcel 047-21-01270