Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Animal Hospital

Approved

Filed May 16, 2026 by Sam Marsh, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
May 16, 2026
Assembly type
RP
Serial number
K317344
Size
4
Test gauge serial
G-1090
Gauge calibration date
Sep 11, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-52-01183
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7001 Stone Gate Ct
Owner: Wexler Holdings LLC
Parcel 059-52-01183