Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Pizza

Approved

Filed Sep 1, 2026 by Cameron Calloway, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Sep 1, 2026
Assembly type
RP
Serial number
B818680
Size
1
Test gauge serial
G-2290
Gauge calibration date
Jun 2, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-47-01244
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6738 Pine Knoll Rd
Owner: Nguyen Holdings LLC
Parcel 059-47-01244