Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7418 Stone Gate Dr

Approved

Filed Dec 27, 2025 by Riley Marsh, Valley Backflow Testing · filed from phone

Report

Date of service
Dec 27, 2025
Assembly type
PVB
Serial number
B265674
Size
1
Test gauge serial
G-9111
Gauge calibration date
Mar 26, 2025
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-89-01048
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7418 Stone Gate Dr
Owner: Drew Kessler
Parcel 059-89-01048