Backflow assembly test · Main Street Car Wash

Approved

Filed Oct 23, 2026 by Quinn Calloway, Evergreen Plumbing & Backflow · filed from phone

Report

Date of service
Oct 23, 2026
Assembly type
RP
Serial number
B895211
Size
1 1/2
Test gauge serial
G-8631
Gauge calibration date
Apr 8, 2026
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-29-01258
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1405 Quarry Ct
Owner: Calloway Holdings LLC
Parcel 059-29-01258