Backflow assembly test · 8529 Cedar Hollow Dr

Approved

Filed Oct 10, 2025 by Hayden Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Oct 10, 2025
Assembly type
RP
Serial number
K688145
Size
3/4
Test gauge serial
G-9014
Gauge calibration date
Jun 23, 2025
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-48-01341
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8529 Cedar Hollow Dr
Owner: Riley Danner
Parcel 069-48-01341