Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6850 Pine Knoll Dr

Approved

Filed Jul 19, 2025 by Logan Whitcomb, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jul 19, 2025
Assembly type
RP
Serial number
W372164
Size
3/4
Test gauge serial
G-3634
Gauge calibration date
Oct 12, 2024
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-44-01158
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6850 Pine Knoll Dr
Owner: Parker Whitcomb
Parcel 069-44-01158