Backflow assembly test · 1473 Sycamore Trl
ApprovedFiled Aug 22, 2026 by Hayden Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Aug 22, 2026
- Assembly type
- DC
- Serial number
- B853290
- Size
- 1
- Test gauge serial
- G-3667
- Gauge calibration date
- May 6, 2026
- Check valve 1
- 6.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-69-01176
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.