Backflow assembly test · 8543 Ridgeview Dr
ApprovedFiled Jun 23, 2025 by Blake Marsh, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jun 23, 2025
- Assembly type
- DC
- Serial number
- A356547
- Size
- 3/4
- Test gauge serial
- G-1766
- Gauge calibration date
- Dec 29, 2024
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 069-57-01087
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8543 Ridgeview Dr
Owner: Sam Fairley
Parcel 069-57-01087