Backflow assembly test · Main Street Dental

Approved

Filed Oct 17, 2023 by Hayden Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Oct 17, 2023
Assembly type
DC
Serial number
K620942
Size
2
Test gauge serial
G-7339
Gauge calibration date
Sep 14, 2023
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-48-01144
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2611 Mill Creek Way
Owner: Pruitt Holdings LLC
Parcel 069-48-01144