Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 234 Laurel Way

Filed Nov 26, 2026 by Blake Marsh, Heritage Backflow Testing · filed from phone

Report

Date of service
Nov 26, 2026
Assembly type
RP
Serial number
B703395
Size
3/4
Test gauge serial
G-9813
Gauge calibration date
Jul 18, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-56-01303
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

234 Laurel Way
Owner: Avery Ramirez
Parcel 069-56-01303